FRL up to 120 minutes Max C4

FACTORY OR SITE INTUMESCENT COATING APPLICATION
Nullifire SC902 Finish
Standard Required
Location Finish Required
External Steelwork Visible
FRL up to 120 minutes Max C4
To Be Confirmed by Client.
  Product Dry Film
Thickness
(Microns)
FRL Thinner
Required
Primer Coat Carbozinc 15-625 75 Microns
Dry Film Thickness
N/A As per TDS
Intermediate Carboguard 635 75 Microns
Dry Film Thickness
N/A As per TDS
Intumescent
Coat
Nullifire SC902 As Per Loading
Schedule
120/--/-- Carboline #10 100% Xylene
Compatible
Topcoat
Carboquick 200 100 Microns
Dry Film Thickness
N/A As per TDS
Compatible
Topcoat
Carboquick 200 100 Microns
Dry Film Thickness
N/A As per TDS
Notes Level of Finish to be approved by the Architect prior to the start of the project. Topcoat also required if the steelwork is to be left in an open construction phase for longer than 3 months maximum. A Stripe coat of Carboguard 635 at 50 microns dft should be applied over the primer coat to all corners, edges, joints etc. A stripe coat of Carboquick 200 at 75 microns dft should be applied over the Nullifire SC902 to all corners, edges, joints etc. Topcoat thicknesses are minimum requirement.