FRL up to 120 minutes C1

FACTORY OR SITE INTUMESCENT COATING APPLICATION
Nullifire SC902 Finish
Standard Required
Location Finish Required
Internal Steelwork Non-Visible
FRL up to 120 minutes C1
To Be Confirmed by Client.
  Product Dry Film
Thickness
(Microns)
FRL Thinner
Required
Primer Coat Carboguard 635 75 Microns
Dry Film Thickness
N/A As per TDS
Intumescent
Coat
Nullifire SC902 As Per Loading
Schedule
120/--/-- Carboline #10 100% Xylene
Optional
Topcoats
Carbothane 133LH 100 Microns
Dry Film Thickness
N/A As per TDS
Notes Level of Finish to be approved by the Architect prior to the start of the project. Optional topcoat required if the steelwork is to be left in an open construction phase for longer than 3 months. A Stripe coat of Carboguard 635 at 75 microns DFT should be applied over the primer coat to all corners, edges, joints etc. Topcoat thicknesses are minimum requirement.

For shop application of Nullifire SC902 the use of Carboquick 200 topcoat will give a more durable finish during transportation and construction.