FRL up to 120 minutes up to C2

FACTORY OR SITE INTUMESCENT COATING APPLICATION
Nullifire SC902 Finish
Standard Required
Location Finish Required
Internal Steelwork Visible
FRL up to 120 minutes C2
To Be Confirmed by Client.
  Product Dry Film
Thickness
(Microns)
FRL Thinner
Required
Primer Coat Carboguard 635 75 Microns
Dry Film Thickness
N/A As per TDS
Intumescent
Coat
Nullifire SC902 As Per Loading
Schedule
120/--/-- Carboline #10 100% Xylene
Compatible
Topcoat
Carbothane 133LH 75 Microns
Dry Film Thickness
N/A As per TDS
Compatible
Topcoat
Carbothane 133LH 75 Microns
Dry Film Thickness
N/A As per TDS
Notes Level of Finish to be approved by the Architect prior to the start of the project. Topcoat also required if the steelwork is to be left in an open construction phase for longer than 3 months maximum. A Stripe coat of Carboguard 635 at 75 microns dft should be applied over the primer coat to all corners, edges, joints etc. An additional coat of Carbothane 133LH may be required depending upon colour of finish chosen Topcoat thicknesses are minimum requirement. For shop application of Nullifire SC902 the use of Carboquick 200 topcoat will give a more durable finish during transportation and construction.